Chilled Water Coil not working
Posted by Richard Raustad, Last modified by Linda Lawrie on 20 April 2010 05:14 PM
It is much easier to use HVACTemplate objects to set up your system. All required supporting objects are set up for you. Notice in your 5Zone input file, you have specified AHU1CCController for BOTH cooling coil controller lists. The second controller list should use controller name AHU2CCController. The 5Zone file worked when I used the correct controller name.

AirLoopHVAC:ControllerList,
AHU1SystemController, !- Name
Controller:WaterCoil, !- Controller Type 1
AHU1CCController; !- Controller Name 1

AirLoopHVAC:ControllerList,
AHU2SystemController, !- Name
Controller:WaterCoil, !- Controller Type 1
AHU1CCController; !- Controller Name 1